What is the Square D by Schneider Electric DPER21 — Adjustable Thermal Overload Relay 12-18A, Three-Phase for?
It's a thermal overload relay for three-phase motors: think of it as the motor's own "reusable fuse," not the wiring's. A panel's breaker or fuse protects the cables against a dead short-circuit (a fast, violent fault) — but if a motor jams mechanically or gets pushed past what it can handle, current rises more slowly and moderately, just enough to quietly cook the windings from the inside without ever tripping a regular breaker. This relay uses three bimetallic strips (two different metals bonded together that curve differently when heated — the same principle behind a clothes iron or an old-style thermostat) wired to each motor line: if the actual current stays above the dial-set value for as long as its "trip class" allows, the strips curve enough to open a small contact that cuts the contactor coil and shuts everything down before the motor burns out.
What should I know before buying it?
Thermal overload relay from the Easy TeSys line, model DPER21, brand Square D by Schneider Electric: adjustable range 12-18A, three-phase, 690V IEC / 600V cUL insulation rating, trip class 10, manual or automatic reset, with its own test button and stop button. It protects the motor (not the line) against sustained overload, phase failure, and phase unbalance through three bimetallic elements that heat up with the actual current on each line and open a 1NO+1NC auxiliary contact wired in series with the contactor coil once the current stays above the dial-set value for the time its trip class allows. Its own screw terminals handle the 3 motor pass-through lines plus the auxiliary control contact — it is not a direct clip-on accessory for this catalog's BAOMAIN contactor (it's designed as a direct-mount accessory for Schneider's own DPE25G7/DP25BL/DPE25U7/DPE25B7 contactors and the Easy TeSys GP2E series, with the LAD7B106 adaptor sold separately), but since it has its own terminals it works just as well wired separately, in series, to any contactor — including this ranking's BAOMAIN — without that mounting piece. The 12-18A range is sized for a three-phase motor up to 7.5kW (10HP) at 690V, or proportionally less at 240V — so the motor's actual full-load amperage (FLA) needs to be calculated before setting the dial, not the contactor's rating. $32.28, 4.6 stars, 6 reviews, #1 in Amazon's "Overload Relays" category — verified live with curl --compressed via the mobile endpoint amazon.com/gp/aw/d/ASIN with an iPhone Safari header (ASIN found via a search at amazon.com/s?k=thermal+overload+relay+bimetallic+contactor through the same endpoint, no captcha block this session): primary-availability-message = "In Stock", 4 of its own add-to-cart-button elements and 124 references to data-csa-c-asin="B09B2PRZBN" on the page, $32.28 price in mobile_buybox_group_1, "Square D by Schneider Electric" brand and "DPER21" model confirmed in prodDetAttrValue next to the same ASIN, rating/reviews in the listing's own acrCustomerReviewLink block ("4.6 out of 5 stars", "6 Reviews") tied to the same ASIN in the details table, no cross-contamination. It was compared against the DPER32 variant (23-32A, $39.99, 4.6 stars, 14 reviews, same manufacturer) from the same search — the DPER21 was prioritized for its amperage range matching this ranking's already-listed 20A BAOMAIN contactor (a motor at that current rating, not the larger one the DPER32 would call for). Also dropped from the same search: four unbranded or weakly-traceable generics — two "JR28-25"/"LR2-D13" compatibles (B0H3T2RJTQ and B0FZ4NH5V4, $18.99 and $19.99, no visible rating or reviews on the listing), a WEG RW27-2D3-U040 (B0HCF83Y7T, $85.00, a recognized brand but also no confirmed review block of its own), and a Shopcorp LR2-D2353 (B0GX7FZLKP, $23.99, 4.6 stars but only 3 reviews and no clear availability message).